Schneider Electric Acti9 iPFK40-T2-3N Surge Arrester 3+1-Pole Type 2 40 kA, A9L15688
60,15 € (48,90 € netto)
The Acti9 iPF K surge arrester with reference number A9L15688 protects electrical installations against the effects of indirect lightning strikes and switching overvoltages. It is a Type 2 surge arrester. It is equipped with an indicator signalling damage after discharging a surge. The Acti9 iPF K arrester can be used in TT and TN-S earthing systems thanks to its appropriate construction, consisting of a summing spark gap in the N-PE path and varistors in the L-N paths. In combination with a fuse cartridge, it can be used with short-circuit currents up to 25 kA. The…
Ships within 3–5 business days · delivery in approx. 5–7 business days
Description
The Acti9 iPF K surge arrester with reference number A9L15688 protects electrical installations against the effects of indirect lightning strikes and switching overvoltages. It is a Type 2 surge arrester. It is equipped with an indicator signalling damage after discharging a surge. The Acti9 iPF K arrester can be used in TT and TN-S earthing systems thanks to its appropriate construction, consisting of a summing spark gap in the N-PE path and varistors in the L-N paths. In combination with a fuse cartridge, it can be used with short-circuit currents up to 25 kA. The maximum discharge current Imax is 40kA. The rated discharge current In is 15kA. Arresters in the 3+1 connection configuration can be used for 3-phase installations. They are characterised by a very low protection level Up <= 1.5 kA.
Technical Data – Class C Surge Arrester
| Mounting Method | 35 mm DIN Rail |
| Number of conductors (excluding earth) | 3 |
| Size | 4 modules |
| Protection level | 1.5 kV |
| Poles | 3+N/PE |
| Maximum continuous operating voltage AC | 340 V |
| Rated discharge current – peak value (8/20) | 15 kA |
| Rated voltage AC | 400 V |
| Network system | TT |
| Protection level L-N | 1.5 kV |
| Operation indication on device | Optical |
| Protection Rating (IP) | IP20 |
| Protection level N-PE | 1.5 kV |
| Max. conductor cross-section (solid/stranded) | 25 mm2 |
| Max. flexible conductor cross-section | 16 mm2 |
| Maximum discharge current (8/20) | 40 kA |
| Short-circuit withstand capacity (Isccr) | 25 kA |
| Maximum Overcurrent Protection, Parallel Connection (Fuse) | 40 A |
| Max. overcurrent protection, series connection (fuse) | 40 A |
Safety instructions: hilark.eu/gpsr/en.
Additional information
| Weight | 0,407 kg |
|---|---|
| Dimensions | 7 × 7 × 6 cm |
| Brand | Schneider Electric |












Reviews