ETI WT-1C NH1C Time-Delay Fuse Link gG 63 A 500 V
6,51 € (5,29 € netto)
Reliable and proven NH fuse-links Knife-type fuse-links – industrial fuse-links are designed to protect electrical power installations against the effects of short circuits and overloads. Their electrical parameters and external dimensions comply with the requirements of the following standards: PN-93/E-06160 (gF), IEC-269, VDE 0636. NH KOMBI fuse-links – a new series of fuse-links with a double operation indicator. The combination of both operation indicators means that both the front indicator and the indicator located on the top cover will activate simultaneously the moment the fuse-link blows. The KOMBI version ensures…
Ships within 3–5 business days · delivery in approx. 5–7 business days
Description
Reliable and proven NH fuse links Knife-contact fuse links – industrial are designed to protect electrical power installations against the effects of short circuits and overloads. Their electrical parameters and external dimensions comply with the requirements of the following standards: PN-93/E-06160 (gF), IEC-269, VDE 0636. NH KOMBI fuse links are a new series of fuse links with a double operation indicator. The combination of both operation indicators means that both the front indicator and the indicator located on the top cover will activate simultaneously the moment the fuse link blows. The KOMBI version provides very good visibility of the fuse link’s operating status both in bases and in fuse switch disconnectors. Technical parameters
Individual identification number assigned by the manufacturer. 004184212
Product type as specified by the manufacturer. NH1C gG 63A/500V
NH – NH knife-contact fuse link
NH1C
Value of current, determined by the manufacturer, that the device can conduct during continuous operation at a specified reference ambient air temperature. 63
AC rated voltage is the electrical voltage value specified for a given device, which is recommended or maximum permissible for correct and safe operation. This value is provided by the device manufacturer and is taken into account in the process of its design and use. 500
DC rated voltage is the electrical voltage value specified for a given device, which is recommended or maximum permissible for correct and safe operation. This value is provided by the device manufacturer and is taken into account in the process of its design and use. 250
Fuse class:
g: Full-range protection. Protection against overload and short circuit.
a: Partial-range protection. Protection against short circuit.
Utilisation category:
G: General-purpose fuse link, for protecting cables, with a time-current characteristic corresponding to former time-delay fuse links (e.g. gG).
B: Fuse link for protecting equipment in underground mines (e.g. gB).
F: Fast-acting fuse link. Manufactured only in Poland (e.g. gF). (Regulation of the Minister of Industry, 1991)
M: Fuse link for protecting circuits supplying electric motors and switchgear (e.g. aM).
Tr: Fuse link for protecting the low-voltage side of power transformers (e.g. gTr).
R: Fuse link for protecting semiconductor devices – diodes and thyristors… (e.g. gR).
S: Fuse link for protecting semiconductor devices – diodes, thyristors… and their supply cables. (e.g. gS)
PV: Fuse link for protecting photovoltaic modules (e.g. gPV).
Bat: Fuse link for protecting storage batteries – energy storage systems (e.g. gBat).
CP: Fuse link for protecting capacitor banks (e.g. gCP). gG
Overcurrent occurring in the event of a short circuit resulting from damage or improper connection in the electrical circuit. 120
single: red spring blade located on the top cover of the fuse link
double: two operation indicators – a red eye located in the central part of the ceramic body, and a red spring blade located on the top cover of the fuse link double
(combined)
Power dissipated in the fuse-link when loaded with rated current In after the fuse-link reaches steady-state temperature. 6.5
Is the sum of the amount of heat Q flowing through the fuse-link during the pre-arcing time and the arcing time, i.e. until the fuse element completely melts and the short-circuit current is interrupted. Numerically, it is the thermal energy that the current in the circuit under consideration would dissipate on a resistance of 1 ohm during the pre-arcing and arcing time. 32000
Is a measure of the quantity of heat Q flowing through the fuse-link during the pre-arcing time, i.e. until the fuse element starts to melt. Numerically, it is the thermal energy that the current in the circuit under consideration would dissipate across a resistance of 1 ohm. 4600
Standards according to which the device was designed, tested and certified. IEC 60269-1,
IEC 60269-2
Product photo
3D
Product advantages
- The fuse body is made of steatite, a thermally stable material. The knife contacts are made of silver-plated brass. The covers are made of aluminium, ensuring long-term corrosion protection.
The body is tightly filled with quartz sand of special granulation, which guarantees high breaking capacity and stability of electrical parameters. - Two operation indicators: a red dot located in the central part of the ceramic body and a red spring-loaded tab located on the top cover of the fuse-link.
- The indicator on the top cover enables cooperation with the NVS 5 microswitch intended for remote signalling of fuse-link operation.
- The contact blades of the fuse-link are silver-plated and shaped to facilitate the installation of the fuse-link in the fuse base or fuse-switch disconnector.
- Insulated fuse handles (NH…/I…) provide additional protection against contact with live parts.
- Insulated handles R 00-3 or GPSHE/AI are used for mounting fuse-links in the fuse base.
- Fuse-links with a striker pin (NH…/K…) are designed to work with HVL, KVL fuse-switch disconnectors equipped with microswitches for remote signalling of fuse-link operation.
- Fuse-links – size NH4 intended for fuse bases have a special design of contact blades to ensure proper contact with the jaw terminals of the fuse base.
- Fuse-links – size NH4a intended only for fuse-switch disconnectors.
Discover NH fuse-links
See the NH fuse-link production line!
Dimensional drawing
ETIsON Curves
Programme functionalities:
- generating and plotting t/I characteristics of protective devices
- adjusting and testing protection settings, examining the impact of changes in the shape of the protection curve
- analysing selectivity between protective devices
- simulating load or short-circuit response of protective devices
- defining operating points and limit conditions from real applications
- preparing reports for design documentation
Check how simple it is!
Technical Data – NH Fuse Link
| Voltage Type | AC |
| Rated Current | 63 A |
| Rated Voltage | 500 V |
| Rated Switching Capacity | 120 kA |
| Size | NH1C |
| Utilisation category in accordance with IEC 60269 | gL/gG (full protection of conductors and cables / full protection of electrical equipment) |
| Trip Indicator Type | Combined (double) indicator |
Safety instructions: hilark.eu/gpsr/en.
Additional information
| Weight | 0,245 kg |
|---|---|
| Dimensions | 13,49 × 2,95 × 6,18 cm |
| Brand | ETI |
| Rated Current | 63 A |